In three phase systems, when all phases are in correct order and
phases
are balanced, Normal LED turns on and the relay is energized.
Missing Phase : When at least one of phases L1, L2, L3 is missing,
phase
off LED turns on and relay de-energizes its contact.
Phase Sequence : If the phase sequence is correct, Relay On LED
turns
on and relay energizes its contact. If phase order is changed, Phase
Off
LED turns on and relay de-energizes its contact.
Phase Voltage Unbalance : Phase-phase voltage unbalance is
adjusted
using the knob located on the front panel of the device. If phase
unbalance
exceeds the adjusted limit, Phase Off LED turns on, relay deenergises its contact .
Voltage Asymmetry Adjustment (Phase Unbalance)(asym.%)
Phase to phase asymmetry is adjusted using the adjustment knob in
the
range of ±%6 .... ±%20 .
- Power Supply:3 x 380 V AC
- Voltage monitoring:5 ~ 15 % ( adjustable )
- Phase loss:Yes
- Phase sequence:Yes
- Phase assymetry:Yes
- Temperature control:PTC
- Max contact current:5 A
- Output:1 C / O
- Dimension (mm):58 x 90 x 35
- Package:10
- Type:FKR2T